An example of the clean, consistently named point list a modernization or documentation engagement delivers.

Illustrative sample

Example data for a fictional facility, shown to demonstrate the deliverable format. Not a real building or client.

A point list records each control point, what it serves, its type and its units. This excerpt shows readable names and descriptions from the fictional example building. Use the naming notes below to interpret it.

Excerpt from the example building

The full deliverable covers all of the roughly 2,400 points in the building, one row per point, grouped by equipment. The excerpt below shows AHU-2 and two of the 46 VAV boxes.

Point nameTypeUnitsNotes
AHU2-SF-STSBIon/offSupply fan status, proven by a current switch
AHU2-SF-CMDBOon/offSupply fan start and stop command
AHU2-SF-SPDAO%Speed command to the supply fan drive, added after the original 1996 installation
AHU2-SATAIdeg FSupply air temperature, duct probe downstream of the fan
AHU2-SAT-SPTAVdeg FSupply air temperature setpoint, reset from outside air temperature
AHU2-MATAIdeg FMixed air temperature, averaging element across the mixing plenum
AHU2-OAD-POSAO%Outside air damper command, economizer section
AHU2-FRZ-ALMBInormal/alarmFreeze protection, wired through the supply fan safety circuit
VAV-2-14-ZNTAIdeg FZone temperature, floor 2, box 14
VAV-2-14-ZNT-SPTAVdeg FOccupied zone temperature setpoint, floor 2, box 14
VAV-2-14-DPR-POSAO%Damper command, floor 2, box 14
VAV-3-08-ZNTAIdeg FZone temperature, floor 3, box 8

In this example, the AO damper points represent commanded position. Measured position feedback, where available, is recorded separately.

Keep the list current as the system changes. Graphics rebuilds, trend expansion, and front-end migration all need a record of the points and their names. Deliver the naming convention with the list so the next person can follow it when adding points.

The naming convention

Every point name is built from the same parts in the same order, so the list sorts by system and equipment and search behaves predictably. A small, consistent set of naming rules makes the list easier to maintain as points are added.

  • System prefix first. AHU for air handlers, VAV for terminal units, HWS for the heating plant, CHLR for the chiller. Every point sorts with its system.
  • Equipment number second. AHU2 is the second air handler. VAV boxes carry floor and box: VAV-2-14 is floor 2, box 14, so the name places the box in the building without opening a drawing, and the two numbers stay hyphen separated so they read at a glance.
  • Component next, where one applies. SF for the supply fan, OAD for the outside air damper, HTG and CLG for the heating and cooling valves, DPR for a terminal unit damper.
  • Point function suffix last, from a fixed set. STS is a status, CMD is a command, SPT is a setpoint, POS is a position, ALM is an alarm, and SPD is a speed reference. Measured air temperatures use the standard abbreviations: SAT, RAT, MAT, OAT, and ZNT for zone temperature.
  • One abbreviation per concept, everywhere. If supply air temperature is SAT on AHU-1, it is SAT on AHU-2 and AHU-3, never DAT on one unit and SA-T on another.
  • The name is for sorting and searching; the description is for people. Every point carries both, and the description says in plain words what the point is and where it lives.

Before and after

The legacy names below are typical of what the 2009 front-end upgrade left behind: difficult to interpret without the original programmer. These are the same points before and after renaming.

Legacy nameStandard nameDescription
SF2STAHU2-SF-STSSupply fan status, AHU-2
SF2SSAHU2-SF-CMDSupply fan start and stop command, AHU-2
AH2VFDAHU2-SF-SPDSupply fan speed command, AHU-2
DA2TAHU2-SATSupply air temperature, AHU-2
DA2TSPAHU2-SAT-SPTSupply air temperature setpoint, AHU-2
MA2TAHU2-MATMixed air temperature, AHU-2
ECO2DMPAHU2-OAD-POSOutside-air damper command, AHU-2
FRZ2AHU2-FRZ-ALMFreeze protection alarm, AHU-2
RM214VAV-2-14-ZNTZone temperature, floor 2, box 14
RM214SPVAV-2-14-ZNT-SPTZone temperature setpoint, floor 2, box 14